All receptacles must be GFCI protected, except if not readily accessible. Or a single receptacle or a duplex receptacle for two appliances located within dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug connected. Or a receptacle supplying only a permanently installed fire alarm or burglar alarm system. -
210.8(A)(5)
At least one receptacle outlet in unfinished basement in addition to any provided for laundry. –
210.52(G)
Nonmetallic wires (cover of wire is not metal) cannot be placed below joists. Must run wires through bored holes, unless 6/2 or bigger, or 8/3 or bigger. -
334.15(C)